Analog input and output parameter group 02
PARAMETER DESCRIPTION 132
5.3.7 Terminal 3-5 signal selection and processing
Choose terminal 3-5 signal specifications, frequency compensation function, and signal polarity .etc.
Parameter
Name
Default Setting Range
Content
02-29
P.531
Terminal 3-5 signal
range selection
0
0
Signal sampling range from 4~20mA.
1
Signal sampling range from 0~10V.
2
Signal sampling range from 0~5V.
02-30
P.508
Terminal 3-5 maximum
operation frequency
50.00Hz
1.00~650.00Hz
50Hz system (00-24(P.189)=1)
60.00Hz
60Hz system (00-24(P.189)=0)
02-31
P.527
Terminal 3-5 filter time
30ms
0~2000ms
---
02-32
P.507
Terminal 3-5
current/voltage signal
bias rate
0.0%
-100.0%~
100.0%
---
02-33
P.545
Terminal 3-5
disconnect selection
0
0
0: Off
1
Inverter decelerates to 0Hz, muti-function digital output
terminal set off alarm
2
Inverter stops immediately, and keypad displays “AEr” alarm
3
Inverter runs continuously according to the frequency
reference before disconnection. Digital output terminal will
set off alarm.
02-34
P.548
Terminal 3-5 minimum
input current/ voltage
0.00V
0~10.00V
---
02-35
P.549
Terminal 3-5 maximum
input current/ voltage
10.00V
0~10.00V
---
02-36
P.546
Percentage
corresponds to
terminal 3-5 minimum
input current/ voltage
0.0%
-100.0~100.0% ---
-400.0%~
400.0%
((02-02)P.504= 2/14/15/16/17)
02-37
P.547
Percentage
corresponds to
terminal 3-5 maximum
input current/ voltage
100.0%
-100.0~100.0% ---
-400.0%~
400.0%
((02-02)P.504= 2/14/15/16/17)
Terminal 3-5 selection and processing
The setting for terminal 3-5 is the same as terminal 4-5.
Note: 1.
Terminal 3-5 disconnection function is only for current disconnection. Please check the setting of parameter
02-29 (P.531) and the position of SW1.
2. Functions mentioned above requires flipping the switch SW1 and setting 02-29(P.531).
Setting