966
FDC-HKXR
System
FDCP2001HKXRE2
FDCP2501HKXRE2
Refer to the selection chart.
1 to 8 units
20.2.2 Range of usage & limitations
Item
Indoor intake air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Single direction piping lenght
Indoor unit MAX 100m
MAX 30m
6 min or more(from stop to stop or from start to start)
3 min or more
Within 10% of rated voltage
MAX 50m
MAX 10m
MAX 15m
Dew point temperature 28 or less, relative humidity 80% or less
Piping length after first division
Number of connected units
Total capacity
11000 to 29200w
13200 to 37100w
When above outdoor unit
When below outdoor unit
Indoor units
that can be
used in
combination
Difference in
height between
indoor and outdoor
units
Difference in height between indoor units
Indoor unit atmosphere (behind ceiling)
temperrature and humidity
1 cycle time
Stop time
Voltage fluctuation
Interval unbalance
Compressor
stop/start
frequency
Power source
voltage
Voltage drop during start
+
_
+
_
Within 3% of rated voltage
+
_
Within 15% of rated voltage
Indoor unit
Individual flow divide controller
First branch
Between the outdoor unit and first branch (main piping): Max 70m (actual length)
Between the first branch and each indoor unit : Max 30m (each indoor unit) (actual length)
The indoor unit and individual flow divide controller positions should be within the range of the reach of the
connections of the wires that come with the individual flow divide contoroller
Note (1)
Allowable length of refrigerant piping, Height difference between indoor and outdoor unit
Outdoor unit
50m
30m
Max
30m
Max
(Max 70m )
15m
Max
(Outdoor unit is lower : 10m)
(Lowest indoor unit)
Individual flow divaide
controller
(Highest indoor unit)
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...