421
FDEN-H
Models
FDC258HEN3A, FDCP258HEN3A, 308HEN3, 308HES3
Required space for maintenance and air flow
Minimum allowable space to the obstacles
Unit:mm
Mark
1
2
3
L
1
Open
Open
500
L
2
300
5
Open
L
3
100
150
100
L
4
5
5
5
Installation
type
Notes
(1) Avoid the location where four sides are entirely
surrounded by walls.
(2) Fix the unit by anchor bolts without fail. Restrict
the protrusion length of anchor bolt to 15 mm
and under.
(3) When strong wind blows against the unit, di-
rect the discharge port at a right angle to the
wind direction.
(4) Secure the space of 1 m and over at the top of
unit.
(5) Make the height of obstruction wall in front of
discharge port lower than the height of unit.
Unit: mm
VIEW A
Liquid piping: ø9.52 (3/8")
(Flare connecting)
Gas piping: ø15.88 (5/8")
(Flare connecting)
40
53
95
40
Liquid piping: ø9.52 (3/8")
(Flare connecting)
Gas piping: ø15.88 (5/8")
Terminal block
Opening for
electric wiring
Opening for
electric wiring
Holes for anchor bolt
(M10
×
4 pcs.)
Holes for drain
(ø9.52
×
3pcs.)
Electric wiring
Opening for piping
and electric wiring
Opening for piping
and electric wiring
Opening for piping
and electric wiring
(Flare connecting)
10
50
380
15
15
55
15
103
150
70
50
47
35
35
110
460
110
195
50
195
40
845
340
880
310
222
40
L
2
L
3
L
4
L
1
Air
inlet
Air inlet
Air outlet
Maintenance
space
150
580
150
50
15
15
50
50
50
50
27
50
15
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...