370
FDT(N)-C
Item
Model
FDT408-A
FDC406CES3
Nominal cooling capacity
(1)
ISO-T1
W
10200/11300
ISO-T3
8900/9900
Power source
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
Cooling input
kW
3.78/3.78/4.65
Running current (Cooling)
A
7.5/7.5/8.8
Power factor (Cooling)
%
77/70/80
Cooling input
kW
4.12/4.12/5.15
Running current (Cooling)
A
8.1/8.1/9.5
Power factor (Cooling)
%
77/71/82
Inrush current (L.R.A)
A
45
Noise level
(4)
dB(A)
Hi:48 Lo:40
57
Exterior dimensions
mm
Unit 320
×
840
×
840
1250
×
950
×
340
Height
×
Width
×
Depth
Panel 30
×
950
×
950
Net weight
kg
34 (Unit:28 Panel:6)
80
Refrigerant equipment
–
RC5547ESE1
×
1
Compressor type & Q’ty
Motor
kW
–
2.61
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
–
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
1.55 [Pre-charged up to the piping length of 5m]
Refrigerant oil
r
–
1.63 (SUNISO 3GS)
High pressure control
High pressure regulator valve
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
2
Motor
W
80
×
1
60
×
2
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
Hi:26 Lo:19
100/110
Fresh air intake
Available
–
Air filter, Q’ty
Long life filter
×
1 (washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
–
Operation control
Wired remote control switch
Operation switch
(Optional:RCD-C-S-E)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
19.05 (3/4
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit.
Optional parts
Decorative Panel
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380/ 415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
Model FDT408CES-A
ISO-T1
ISO-T3
Notes (1) The data are measured at the following conditions.
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
FDT408CES-A
Operation data
(3)
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...