369
FDT(N)-C
Item
Model
FDT308-A
FDC306CES3
Nominal cooling capacity
(1)
ISO-T1
W
7100/7700
ISO-T3
5700/6000
Power source
3 Phase, 380-415V 50Hz or 380V 50Hz/415V 50Hz, 380V 60Hz
Cooling input
kW
2.83/2.84/3.35
Running current (Cooling)
A
5.3/5.3/6.0
Power factor (Cooling)
%
81/75/85
Cooling input
kW
3.02/3.03/3.58
Running current (Cooling)
A
5.7/5.7/6.5
Power factor (Cooling)
%
80/74/84
Inrush current (L.R.A)
A
43
Noise level
(4)
dB(A)
Hi:41 Lo:35
59
Exterior dimensions
mm
Unit 260
×
840
×
840
844
×
950
×
340
Height
×
Width
×
Depth
Panel 30
×
950
×
950
Net weight
kg
30 (Unit:24 Panel:6)
67
Refrigerant equipment
–
RC5538ESE1
×
1
Compressor type & Q’ty
Motor
kW
–
2.24
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
–
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
1.3 [Pre-charged up to the piping length of 5m]
Refrigerant oil
r
–
1.63 (SUNISO 3GS)
High pressure control
High pressure regulator valve
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
1
Motor
W
30
×
1
60
×
1
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
Hi:17 Lo:12
54/56
Fresh air intake
Available
–
Air filter, Q’ty
Long life filter
×
1 (washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
–
Operation control
Wired remote control switch
Operation switch
(Optional:RCD-C-S-E)
- (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit.
Optional parts
Decorative Panel
Model FDT308CES-A
Internal protector for compressor.
Internal thermostat for fan motor.
Internal Pressure relief valve for compressor.
Operation data
(3)
ISO-T3
ISO-T1
FDT308CES-A
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
ISO-T1, JIS B8616
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380/415V 50Hz and 380V 60Hz respectively.
(4) Indicates the value at mild mode.
Notes (1) The data are measured at the following conditions.
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...