SCM-HG
(4 room)
132
(5)
Comfort timer setting
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode
operation is selected, the comfort timer starts and determines the starting time of next operation based on the initial value of 15
minutes and the relationship between the room temperature at the setting time (temperature of room temperature sensor) and the
setting temperature. (Max. 60 minutes)
Operation mode
Operation start time correction value (Min.)
3 < Room temp. – Setting temp.
1 < Room temp. – Setting temp. 3
Room temp. – Setting temp. 1
At cooling
+5
No change
–5
3 < Setting temp. – Room temp.
2 < Setting temp. – Room temp. 3
Setting temp. – Room temp. 2
At heating
+5
No change
–5
Notes (1) At 5 minutes before the timer ON time, operation starts regardless of the temperature of the room temperature sensor (Th1).
(2) This function does not actuate when the operation select switch is set at the dehumidifying as well as the dehumidifying in the auto mode.
However, the operation of item (1) above is performed during the dehumidifying in the auto mode.
(3) During the pleasant reservation operation, both the operation lamp and timer lamp illuminate and the timer lamp goes off after expiration of the timer, ON setting
time.
¡
If the difference (= Setting temperature – Room temperature) is 4ºC, the correction value is found to be +5 minutes from the
table shown above so that the starting time of next operation is determined as follows:
15 min. e 5 min. = 20 min. earlier
Current operation
Correction value
start time
Corrects the starting time of next operation by
calculating the temperature difference.
(Example) Heating
Setting temperature
Room temperature
Operation starting time
Time
Setting time
15 min.
10 min.
5 min.
earlier
earlier
earlier
(c)
Swing flap
Flap moves in upward and downward directions continuously.
Horizontal
blowing
(b) Memory flap (Excepted 22, 25models)
While the flap is operating if the AIRFLOW button is pushed once, it stops swinging at an angle.
As this angle is memorized in the microcomputer, the flap will be automatically set to the angle when next operation is
started.
◆
Recommendable stopping angle of the flap
Slant forward
blowing
COOL•DRY
HEAT
¡
Wall mounted type
¡
Ceiling recessed type
¡
Wall mounted type
¡
Ceiling recessed type
≤
≤
≤
COOL•DRY
HEAT
Horizontal
blowing
Slant forward
blowing
≤
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...