FDC-HKX
846
Vinyl tube
A. If there is a ceiling
1)
Open the hole in the installation location to the ceiling
opening dimensions.
2)
Install the suspension bolts (procured locally) at the
designated locations.
(Use care as the center of the spacing for the suspension
bolts is not at the center of the panel.)
3)
Hang the unit, use the four bolts to mount the pattern
paper provided to the panel mounting section and adjust
the height.
Outlet
port
Printed surface
Ceiling surface
Pattern paper
Adjust the position of the main unit so that
the bottom surface of the pattern paper and
the bottom surface of the ceiling align.
Panel mounting position
<Panel mounting position>
5)
After confirming the above, secure the unit in position.
4)
Use a level or transparent hose with water in it to
confirm that the unit is level. If the unit is not level,
problems such as water leakage or improper operation
of the float switch could occur.
B. If ceiling is to be installed later
1)
Follow steps A2 to A4 in the previous section "A. If
there is a ceiling" to install the unit and mount the
pattern paper.
2)
When the ceiling is installed, the outer perimeter of
the pattern paper can be referred to for making the
opening in the ceiling.
3)
After checking the height and that the unit is level,
secure the unit in position.
<Pattern paper mounting configuration>
(d) Drain piping
1)
Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or making traps.
●
Good piping
●
Improper piping
1.5 m ~ 2 m
Suspension
bolts
Heat
insulation
A downhill grade
of 1/100 or more
Air vent
Avoid riding across an elevation
Keep free from traps
Do not pipe under water.
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...