FDC-HKX
934
5
4
6
~
~
~
1
2
3
Normal LED2 check: If it flashes, the
microcomputer operates normally.
CNL
1 2 3 7 8 9
1 3
14
15 19 2
0
21
22 23
24
25
CM
U
V
W
CnW
2 1
+
–
+
–
+
–
CNR
LD1
Green
*
LED1 (Green)
It is normal if it flashes at each 0.5-
second.
LD2
Red
CNI2
CNI1
Transformer
Control PCB
CNA1
CNA2
LED1
Red
LED2
Green
6
7
5
Unit: V(AC)
*
DC540V
4
3
TB
L1
L2
L3
N
52C
R1
1
2
3
4
5
6
7
1
2
3
4
5
6
7
2
*
Connector
Detail of communication
CN11
1
2
3
4
Common
12V power supply
Transmission to inverter
Receiving from inverter
V (Analog tester)
Watchdog (Communication from
invert PCB to outdoor PCB)
Inverter overheat
Current cut
0V
12V
Swings between 11 ~ 11.5V
Swings between 4.5 ~ 5V
Swings between 2 ~ 4V
It is normal if 5V or abnormal
if 0V
It is normal 5V or abnormal if OV
5
6
7
• Communication checked at the CN11 will show the following values.
LED2 (red) check
1 time flash
: Power transistor overheat
• Stop operation and wait till temperature
drops.
2 time flashes
: Current cut (power transistor over-current)
• Short-circuited compressor wiring
• Trouble on inverter PCB
• Trouble on power transistor
Keeps flashing: Transmission error between inverter and
outdoor unit
• Connector CN11 or CN12 is disconnected or
broken wire between connectors.
• Error on outdoor control PCB
• Error on inverter PCB
* Check points of outdoor unit
Check with power ON at the points marked with *.
Turn power OFF before starting inspection.
Also remove each part before starting inspection.
Inspection of power cables:
There must be continuity on the cables. Cables
must be connected properly.
Mark
Tester probe
(Red)
Tester probe
(Black)
Noise filter check: There must be a continuity.
Fuse check: There must be continuity.
Check of power supply
Check the power sup-
ply on L
1
, L
2
and L
3
of terminal block TB.
(It is normal if AC
380V is detected.)
•
*
Noise filter
7-segment
indicator
Reactor continuity check
Continuity check after disconnecting the
connector: There must be continuity.
Resistor R1 check: Mea-
sure the resistance value.
FDC140
FDC224
FDC280
30
Ω
30
Ω
30
Ω
Are there any abnormality such as crack, burn, etc. in appearance?
Diode module check
If tester probes are inverted,
the connection becomes
open.
Tester probe
+
~
6
-
5
~
If good
Continuity
Capacitor check
Check for abnormality in appear-
ance such as damage, swell, etc.
Check the charging characteristics
with a tester.
It is normal if the needle swings
followed by a gradual return and,
when tested again after changing
the polarity, the needle returns
again.
Power transistor output check
Measure the output voltage after disconnecting the fasten terminal from the compressor.
(Values of output voltage indicate those obtained when no load is applied to the inverter.)
Type
All types (outdoor)
35Hz
160~180
40Hz
180~210
65Hz
290~320
75Hz
330~360
95Hz
380~410
Frequency
Notes
(1) Confirm that all voltages measured between U-K, V-W and W-U are same.
(2) Values listed above are those obtained using a digital tester after disconnecting the terminals on
the compressor. The values vary depending on the kinds of measuring instrument.
Power transister module
Inverter PCB
Transformer check: There must
be continuity at the primary side
after disconnecting the connec-
tor CNAI.
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...