1073
FDC-HKXR
Error
Are the return air
temperature and Center/
Remote displayed on the
remote controller?
Power switch OFF
Power supply line error
Check the error
code displayed
ON/OFF
switch OFF
Microcomputer
out of control
Power supply line error
See page 1077
Cause is accidental (noise, etc.)
and the unit is normal.
ON/OFF
switch OFF
Check of error code
Is any error
code display?
Does the error
code disappear?
Does the error repeat
YES
YES
NO
NO
YES
NO
YES
NO
YES
NO
Turn off the wiring breaker (power
supply) and back on again 1min. later. (Power supply reset)
Errors due to external noise, etc.
Error code may be displayed or the error may not be displayed normally even if the controller is normal because of external noise
source
(1)
or joined or parallel arrangement of power cables and signal wires. It is because the wire of remote controller, wired
remote controller signal wires for multiple units or the network signal wires may be influenced by external noises whitch are
judged as signals by the microcomputer whitch reacts mistakenly.
When there is any noise source, it is necessary to the shield wire for the remote controller and signal wires.
Note (1) High frequency medical machine, rectifier motor application device, thyristor, broadcast transmission tower, power
transmission line, power line of electric train, automatic door motor, elevator (voltage drop), wireless telephone, high
voltage power distribution line, computer, personal compouter and their cables.
There do not necessarily always cause problems but they can be a source of electrical noise.
(a) Diagnosis by the power supply reset
When any error occurs, reset the power supply as described below to see if it is the result of accidental noise, etc.
Check at the indoor unit side.
Does start operation
with display of cool-
ing degree: Hi, ther-
mostat: 23
°
C?
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...