269
FDT(N)-H
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
(4) Indicates the value at mild mode.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1, JIS B8616
Operation data
(3)
Item
Model
FDTN258H
FDC258HEN3A
Nominal cooling capacity
(1)
W
5700
Nominal heating capacity
(1)
W
6100
Power source
1 Phase, 220/240V, 50Hz
Cooling input
kW
2.05/2.16
Running current (Cooling)
A
9.4/9.4
Power factor (Cooling)
%
99/96
Heating input
kW
1.95/2.10
Running current (Heating)
A
9.1/9.2
Power factor (Heating)
%
97/95
Inrush current (L.R.A)
A
51
Noise level
(4)
dB(A)
Hi: 39 Lo: 35
52
Exterior dimensions
mm
Unit 260
×
840
×
840
845
×
880
×
340
Height
×
Width
×
Depth
Panel 30
×
950
×
950
Net weight
kg
30 (Unit:24 Panel:6)
55
Refrigerant equipment
–
RM5526GNE4
×
1
Compressor type & Q’ty
Motor
kW
–
1.9
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & bare tubing
Refrigerant control
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
1.1 [Pre-charged up to the piping length of 5m]
Refrigerant oil
r
–
0.7 (BARREL FREEZE 32SAM)
Defrost control
MC controlled de-icer
High pressure control
High pressure switch
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
1
Motor
W
25
×
1
55
×
1
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
Hi:16 Lo:11
56
Fresh air intake
Available
–
Air filter, Q’ty
Long life filter
×
1(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wireless remote control switch
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Abnormal discharge temperature protection
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Wireless remote controller. Drain hose
Optional parts
Decorative Panel
FDTN258HEN-S1
Model FDTN258HEN-S1
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...