Drainage Test
When using the standard drain port, execute a drainage test after completion of electric work.
1
During the test run, make sure that drain flows properly through the piping and that no water leaks from connections.
2
Be sure to conduct this test even when the unit is installed in the heating season.
3
In case of a new building, conduct the test before it is furnished with the ceiling.
1)
Inject about 1,000cc by using a feed water pump from the grommet on the drain pump side.
2)
At the drain port (transparent portion), check if drainage is performed.
3)
After completion of the drain test, completely perform heat insulation fot the drain pipe up to the main unit.
(g) Fixing of Panel ( The panel fixing bolts are attached on the panel. )
Note (1) Care should be exercised in handling the supply air port on the panel because it is easily depressed by finger nail.
1)
Check with the accessory level gauges that the indoor unit height and the size of ceiling hole are correct.
Notes (1) Remove the level gauge from the indoor unit befroe fixing the panel.
(2) Remove the Air inlet panel from the panel proper.
Procedure for Dismounting the Air inlet Panel
Air inlet panel
Panel proper
Remove
Pin (B)
Pin (A)
Panel outer frame
Panel inner frame
Insert the tip of the supply water pump approximately
50 mm in a downward direction.
Piping penetration cover
Note (1) If the connector remains connected, drain water is discharged from the standard pipe connecting port, leading to water
leakage.
Clear flexible tubing (optional)
Hard vinyl chloride piping.
General piping VP-20
Heat
insulation
Rubber plug
Remove
Control box
Natural drain port
CNR (Blue·2P)
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...