195
SCM-HG
(2 room)
(7)
Heating Operation
(a)
Summary
1)
Capacity control
Model
Capacity
SCM452HENG-L
2.2 ~ 6.0 kW
28 rps or less
More than 28 rps, but 134 rps or less
More than 140 rps
Decision speed
28 rps
28 to 134 rps
134 rps
Indoor unit instruction total speed value
Capacity control is within the range shown above. If demand capacity of the indoor units exceeds the maximum
capacity of the outdoor unit, the demand capacity will be proportionally distributed.
2)
Outdoor unit speed control
(28 ~ 134 rps)
Note (1) The indoor unit instruction total speed value is the total of the values from each unit in item (b).
(c)
Operation of Major Functional Components in Cooling Mode
Functional
components
Operation
Instruction speed
Indoor
unit fan
Compressor
Outdoor unit fan
Electronic
expansion valve
See preceding table
ON
According to instruction speed
According to outdoor unit speed
According to decision
speed
0
(All indoor units)
OFF
According to stop mode
According to mode switching
OFF
0
(Thermostat off units)
ON
All closed
(Thermostat off units)
According to outdoor unit speed
According to mode switching
All closed
(Fan, stop, abnormal stop units)
0
(Fan, stop, abnormal stop units)
0
(All units)
ON
First speed or low
OFF
OFF
According to stop mode
Cooling
Thermostat OFF
(All indoor units)
Thermostat OFF
(Some of indoor units)
Fan, stop, abnormal stop
(Some of indoor units)
Failure
(Outdoor Unit)
Fixed
Automatic
(b)
Mode switching
Within the selected mode, the unit operates using the values shown below which were obtained by multiplying a conversion
coefficient to the indoor unit instruction speed.
(c)
Operation of Major Functional Components in Heating Mode
Model (Indoor)
Operation Mode
Automatic
High
Medium
Low
Hi power
Econo
28 ~ 74
28 ~ 74
28 ~ 50
28 ~ 34
76
28 ~ 42
28 ~ 80
28 ~ 80
28 ~ 58
28 ~ 36
82
28 ~ 44
28 ~ 120
28 ~ 120
28 ~ 86
28 ~ 46
120
28 ~ 60
28 ~ 126
28 ~ 126
28 ~ 92
28 ~ 46
120
28 ~ 54
28 ~ 134
28 ~ 134
28 ~ 126
28 ~ 54
126
28 ~ 64
22
25
28
32
40
(rps)
Functional
components
Operation
Instruction speed
Indoor
unit fan
Compressor
Outdoor unit fan
Electronic
expansion valve
See preceding table
ON
According to mode switching
According to instruction speed
According to outdoor unit speed
According to decision
speed
0
(All indoor units)
OFF
According to stop mode
Hot Keep
Hot Keep
OFF
0
(Thermostat off units)
ON
After 4 minutes all closed: 58 pulse
(Thermostat off units)
According to mode switching
According to instruction speed
According to outdoor unit speed
58 Pulse
(Fan, stop, abnormal stop units)
0
(Fan, stop, abnormal stop units)
0
(All units)
ON
OFF
Hot Keep
Hot Keep
OFF
According to stop mode
Heating
Thermostat OFF
(All indoor units)
Thermostat OFF
(Some of indoor units)
Fan, stop, abnormal stop
(Some of indoor units)
Failure
(Outdoor Unit)
Fixed
Automatic
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...