1088
FDC-HKXR
(4) Proceduer for checking the outdoor unit irrespective of indoor/outdoor transmission
Turn off the outdoor unit power supply
Set 45 in outdoor unit No.
Turn ON the outdoor unit PCB(SW
3-7
)
Turn ON the outdoor unit power supply
Turn OFF the outdoor unit power supply
Return outdoor unit NO. to the installation state.
Defective outdoor unit PCB
Open the 63H
1
Defective 52C
Defective outdoor unit PCB or
indoor unit PCB
(Or pull out the connector CnA
2
on the outdoor unit PCB)
(When connecting the CnA
2
on the outdoor unit PCB)
(Pull out Faston No.17 on the PCB)
Is the 52C
turnd ON?
Does a voltage
Appear at the 52C coil.
Can the compressor
operate at 35Hz?
(Continued to the previous page)
Note (1) When using this procedure, the indoor unit enters a transmission error state. In the indoor unit the expansion valve may be closed or
the fan may stop.
Note( 1)
After the compressor is operated, stop it at once.
Note (1)
Otherwise, it will cause a failure to the compressor.
YES
NO
YES
NO
YES
NO
1
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...