410
FDEN-H
(2)
Alternative refrigerant R407C use models
Model FDENP208HEN-S
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
(4) Indicates the value at mild mode .
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1, JIS B8616
Operation data
(3)
Item
Model
FDEN208H
FDCP208HEN3A
Nominal cooling capacity
(1)
W
5000
Nominal heating capacity
(1)
W
5400
Power source
1 Phase, 220/240V, 50Hz
Cooling input
kW
2.08/2.15
Running current (Cooling)
A
9.5/9.6
Power factor (Cooling)
%
99/93
Heating input
kW
1.98/2.12
Running current (Heating)
A
9.3/9.5
Power factor (Heating)
%
97/93
Inrush current (L.R.A)
A
55
Noise level
(4)
dB(A)
Hi: 43 Lo: 38
52
Exterior dimensions
mm
184
×
1000
×
650
690
×
880
×
290
Height
×
Width
×
Depth
Net weight
kg
22
49
Refrigerant equipment
–
RM5523HNE5
×
1
Compressor type & Q’ty
Motor
kW
–
1.7
Starting method
–
Line starting
Heat exchanger
Louver fines & inner grooved tubing
Slitted fines & bare tubing
Refrigerant control
Capillary tube
Refrigerant
R407C
Quantity
kg
Holding charged
0.98 [Pre-charged up to the piping length of 0m]
Refrigerant oil
r
–
0.7 (MA32)
Defrost control
MC controlled de-icer
High pressure control
High pressure switch
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
2
Propeller fan
×
1
Motor
W
40
×
1
55
×
1
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
Hi:14 Lo:10
56
Fresh air intake
Unavailable
–
Air filter, Q’ty
Polypropylene net
×
2 (washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Operation switch
Wireless remote control switch
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Thermostat for discharge temperature.
Installation data
mm
Liquid line:
φ
6.35 (1/4
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP20)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Wireless remote controller
Optional parts
–
FDENP208HEN-S
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...