360
FDT(N)-H
5
The discharge gas temperature is too high. (Only case of FDC(P)208~508 type)
4
The outdoor heat exchanger temperature is too high (70
°
C or over)
Are the heat
exchanger thermistor
Charateristisc
Normal?
YES
NO
NO
Heart exchanger thermistor
replacement
Is the unit
normalized
Defective outdoor unit
PCB Replacement
(Defective heat exchanger
thermistor input circuit)
Cooling, overload
operation?
Check the unit side closely
• Is outdoor fan motor operating?
• Is the outdoor unit shortcircuited?
• Is the installation space adequate?
• Is there too much refrigerant?
Reset
Error stop
60
°
C
70
°
C
Outdoor unit heat exchanger temperature
(1)
(1)
Note (1) Outdoor unit heat exchanger thermistor detects
the state of cooling overload operation.
Outdoor unit
Red LED
Green LED
4 time flashes
Stays OFF
Temperature
15
10
5
0
°
C 10
°
C
30
°
C 40
°
C
20
°
C
50
°
C
5k
Ω
at 25
°
C
Is the outdoor
unit heat exchanger
themistor connector
OK?
Repair
NO
YES
NO
YES
Are the outdoor
unit heat exchanger themistor
characteristics OK, is there
any broken wire?
Defective outdoor unit
heat exchanger thermistor
Replacement
Defective outdoor unit PCB
Replacement (Defective
outdoor unit heat exchanger
thermistorinput circuit)
Outdoor unit heat exchanger
thermistor (Th
O-
R) Resistance
temperature characteristics
Resistance
(k
Ω
)
Note (1) 22k
Ω
at -6
°
C
6
Defective outdoor unit heat exchanger thermistor
Outdoor unit
Red LED
Green LED
1 time flash
1 time flash
Outdoor unit
Red LED
Green LED
5 time flashes
Stays OFF
Is the
discharge gas ther-
mistror characteristics
normal?
YES
NO
NO
Discharge pipe thermis-
tor replacement
Is the unit
normalized
Defective outdoor unit
PCB Replacement
(Defective discharge gas
thermistor input circuit)
Discharge gas
temperature error?
(At cooling/heating
operation)
Check the unit side.
Check the unit side.
•
Insufficient refrigerant
Charge the refrigerant (measure)
•
Is it the overload operation?
Operable
Error stop
90
°
C
135
°
C
Discharge pipe temp.
•
During cooling: Is FMo operating?
•
During heating: Is FM
I
operating?
Are control valves (both liquid,
gas) fully opened during both
cooling and heating.
•
Is the installation space of indoor/
outdoor units adequate?
•
Is there any short circuit air flow
for indoor/outdoor units?
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...