591
FDU-H
Item
Model
FDU508-A
FDC506HES3
Nominal cooling capacity
(1)
ISO-T1
W
12500/14000
ISO-T3
11900
Nominal heating capacity
(1)
ISO-T1
W
12800/14400
Power source
3 Phase, 380-415V 50Hz, 380V 60Hz
Cooling input
kW
5.01/5.03/6.03
Running current (Cooling)
A
10.3/10.3/11.5
Power factor (Cooling)
%
74/68/80
Heating input
kW
4.63/4.67/5.61
Running current (Heating)
A
9.5/9.6/10.7
Power factor (Heating)
%
74/68/80
Cooling input
kW
6.63
Running current (Cooling)
A
12.5
Power factor (Cooling)
%
81
Inrush current (L.R.A)
A
68
Noise level
dB(A)
45/47
59
Exterior dimensions
mm
360
×
1200
×
830
1250
×
950
×
340
Height
×
Width
×
Depth
Net weight
kg
62
91
Refrigerant equipment
–
RC5563ESE2
×
1
Compressor type & Q’ty
Motor
kW
–
3.73
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & bare tubing
Refrigerant control
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
2.3 [Pre-charged up to the piping length of 5m]
Refrigerant oil
r
–
2.07 (SUNISO 3GS)
Defrost control
IC controlled de-icer
High pressure control
High pressure regulator valve
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
2
Propeller fan
×
2
Motor
W
230
×
1
60
×
2
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
34/40
100/110
Available static pressure
Pa
Standard: 100 (10), Max 200 (20)
–
(mmAq)
Fresh air intake
Available
–
Air filter, Q’ty
Field purchased
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
40 (Crank case heater)
Operation control
Wired remote control switch
Operation switch
(Optional: RCD-H-E)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
19.05 (3/4
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit.
Optional parts
–
Operation data
(3)
Model FDU508HES-A
ISO-T1
ISO-T3
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1, JIS B8616
Cooling
29˚C
19˚C
46˚C
24˚C
ISO-T3, SASO
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 380V 50Hz/415V 50Hz/380V 60Hz.
Notes (1) The data are measured at the following conditions.
FDU508HES-A
Internal protector for compressor.
Internal thermostat for fan motor.
Internal pressure relief valve for compressor.
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...