FDC-HKX
930
(ii) When the compressor does not operate although the remote controller display is normal (Without the
check display)
Take following steps first before confirming the following items:
•
Confirm that it is normal at the indoor unit side, LED1 (green) keeps flashing on the outdoor unit control PCB and LED2
(red) is not lit.
•
When LED1 (red) is flashing while the remote controller display is normal, LED2 (red) can be turned off if SW
3-1
is turned
ON and turned OFF again.
Note (1) Be sure to turn the SW
3-5
off after the confirmation.
Notes (1) Expansion valve of the indoor unit may be closed or the indoor fan may be stopped. Stop the compressor no sooner than it has started. Neglecting
this caution could result in compressor trouble.
(2) Method to check with the outdoor unit only is described on the next page.
Turn on SW
3-5
(test run) on the outdoor
contorol PCB.
(Refer to page 819)
NO
NO
NO
YES
YES
NO
YES
YES
YES
YES
NO
NO
Is 52C turned ON?
Replace 52C.
Does compressor
(1)
operate?
Does LED1 (green) on
inverter PCB flash?
Do 7 SEG on out-
door unit PCB indicate
20Hz or higher?
NO
YES
Does LED2 (red) on
inverter PCB light
or flash?
Is voltage detected
between U,V,W on
power transistor?
Defective inverter
Defective compressor
Note(1) Set 7 SEG indicator changeover
swich (SW
4
) to 0.
Defective inverter
Is voltage detected on
52C coil?
Outdoor unit control
PCB is defective.
• Is indoor return air thermistor normal?
• Is thermostat stopped?
Check error display again.
(See page 933.)
Diagnose errors on
LED's on inverter
PCB.
It is designed to transmit the highest request frequency from the
outdoor to the indoor regardless the state of thermostat. It will not
operate therefore if the transmission is not normal between the
outdoor and the indoor.
When it is turned on with SW
3-5
(test run), there is no error display
unless the indoor unit is connected. In such occasion, operate the
system with the remote controller and check if E3 (no counterpart)
or E5 (transmission error) is transmitted or not.
•
•
1
(From next page)
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...