FDT(N)-H
(5)
Electrical wiring
™
This air conditioning system should be notificated to supply authority before connection to power supply system.
(a)
Selection of size of power supply and interconnecting wires.
¡
Select wire sizes and circuit protection from Table 2.
Table 2 ( This table shows 20m length wires with less than 2% voltage drop. )
Drain elbow (1 pc.)
(local procurement)
™
There are 3 holes (ø 20) on the bottom plate of Outdoor
unit for draining condensed water.
™
To guide the condensed water to the gutter it is neces-
sary to install the unit on the flat base or blocks.
™
Connect the drain elbow as shown in the illustration and
close other holes with grommets.
Drain grommet
(2 pcs.)
Hard vinyl chloride pipe for
general purpose (VP-16)
(local procurement)
Interconnecting
wires
Circuit breaker
Earth leakage
breaker
Outdoor
unit
Indoor
unit
HIGH VOLTAGE
(b)
Wiring connection.
1)
Connect the same terminal number between the Indoor unit and Outdoor unit as shown in the following diagram.
2)
Make wiring to supply to the Outdoor unit, so that the power for the Indoor unit is supplied by
1
and
2
terminals.
3)
Secure the wiring with wiring clamp so that no external force is transmitted to the connecting portion of terminal.
4)
There is a ground (Earth) terminal in the control box.
Interconnecting
wires
Circuit breaker
Earth leakage
breaker
Outdoor
unit
HIGH VOLTAGE
Indoor
unit
(a)
1 phase model
O
IMPORTANT
¡
Electric wiring work should be conducted only by authorized personnel.
¡
Use copper conductor only.
¡
Power source wires and Interconnecting wires shall not be lighter than polychloroprene
sheathed flexible cord (design HO5RN-F IEC 57).
¡
Do not connect more than three wires to the terminal block.
¡
Use round type crimped terminal lugs with insulated grip on the end of the wires.
(b)
3 phase model
Following precautions must be observed when the model is adapted to R407C.
(1) Tools and related components should be changed when handling a different kind of refrigerant in order to prevent mixing of
different oils.
Gauge manifold and charge hose, particularly, should never be used after using them for R22.
(2) Charge cylinder should not be used. Otherwise, the refrigerant composition may change when charging R407C into the cylinder.
(3) Refrigerant should be charged in the liquid phase from the container. Charging the refrigerant in the gaseous phase could change
the refrigerant composition substantially.
(4) Volume of refrigerant to be taken out in the liquid phase from the container should be up to 90% of necessary quantity (in weight
percent) as a standard.
(5) Refrigerant should not be replenished even if a leakage is discovered because it could change the refrigerant composition
substantially.
When a leakage is discovered, replace with new refrigerant in the specified volume. However, it could be replenished temporarily
in case of an emergency.
(4)
Drain piping work
¡
Execute the drain piping by using field purchased parts of pipe, elbow, and grommets, if the drainage work is needed.
Item
Model
FDC(P)208 type
FDC(P)258 type
FDC(P)308 type
FDC(P)308 type
FDC(P)408 type
FDC(P)508 type
FDC808 type
FDC1008 type
Phase
1
3
30
50
20
30
15
20
50
Circuit breaker
Switch breaker
(A)
Over-current protector
rated capacity (A)
Power source
wires
(minimum)
Interconnecting
and grounding
wires (minimum)
5.5mm
2
ø 2.0 mm
5.5mm
2
8.0mm
2
ø 1.6
20mm
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...