FDC-HKX
889
¡
Branch pipe set shapes
(2) Table for selection of piping size
FDC 140 type
Model
Item
Outdoor unit
Main piping
No. 1 branch
Less than 101
101 to less than 180
180 or more
Gas line
Liquid line Branch used
φ
19.05
φ
19.05
φ
19.05
φ
15.88
φ
19.05
φ
9.52
φ
9.52
φ
9.52
φ
9.52
DIS-2KX20-E
DIS-2KX10-E
DIS-2KX20-E
FDC 224 type
Gas line
Liquid line Branch used
φ
25.4
φ
25.4
φ
25.4
φ
15.88
φ
19.05
φ
25.4
φ
12.7
φ
12.7
φ
12.7
φ
9.52
φ
12.7
DIS-2KX30-E
DIS-2KX10-E
DIS-2KX20-E
DIS-2KX30-E
DIS-2KX30-E
DIS-2KX10-E
DIS-2KX20-E
DIS-2KX30-E
FDC 280 type
Gas line
Liquid line Branch used
φ
28.58
φ
28.58
φ
28.58
φ
15.88
φ
19.05
φ
25.4
φ
12.7
φ
12.7
φ
12.7
φ
9.52
φ
12.7
Model Item Mark
Branch pipe
Item Mark
Reducer
DIS-2KX30-E
DIS-2KX20-E
DIS-2KX10-E
Gas line
Liquid line
Gas line
Liquid line
Gas line
Liquid line
Gas line
Liquid line
Gas line
Liquid line
Gas line
Liquid line
1
2
3
4
7
8
Notes
Notes
(1) If adjustment is required between the branch connection and the unit port, always make the adjustment on the branch connection side.
(2) The selection of piping size and branch piping, total all the indoor unit down flow capacity for that piping and branch piping.
(1)The gas side flow divider pipe is insulated.
(2)Cut piping in the center on site in the area it will be used.
Total indoor unit
down-flow capac-
ity after the sec-
ond branch.
5
6
70
ID
25.4
OD
19.05
70
ID
28.58
OD
25.4
424
94.5
ø
15.88
ø
12.7
ø
15.88
370
87
ø
9.52
ø
6.35
ø
9.52
370
87
ø
9.52
ø
6.35
ø
9.52
424
94.5
ø
12.7
ø
15.88
ø
12.7
ø
15.88
ø
19.05
ø
19.05
519
118
ø
15.88
ø
19.05
ø
12.7
ø
15.88
ø
19.05
ø
25.4
ø
25.4
ø
28.58
370
87
ø
9.52
ø
12.7
ø
9.52
ø
12.7
ø
6.35
ø
9.52
ø
12.7
ID
ID
ID
ID
ID
ID
ID
ID
ID
ID
ID
ID
ID
ID
ID
Diameter is same as above dimensions
Diameter is same as above dimensions
Diameter is same as above dimensions
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...