MAINTENANCE DATA
2.6.1
Trouble shooting
(1)
Trouble shooting to be performed prior to exchanging PCB, (Printed circuit board) [Common to all models]
All the models described in this chapter are controlled by a microcomputer. When providing maintenance service to customers it
is necessary to understand the function controlled by a micro computer thoroughly, so as not to mistakenly identify correct opera-
tions as mis-operations. It is also necessary to perform the following simple checks before conducting detailed checks or exchang-
ing printed circuit board.
Before exchanging Printed circuit board
Claim call from the user
Ascertain the nature of the claim.
Ascertain the operation status.
Does the trouble occur again?
Is this nonsense claim?
Operate the unit.
Does the trouble occur again?
Temporarily turn off the power source and
turn it on again in about 1 min. and turn the
unit on again.
YES
No
YES
YES
Does the trouble occur again?
Disconnect connectors and connect them
again.
Operate the unit again after confirming that the fuse
and the varistor equipped on PCB does not burn out.
Carry out checks according to detailed
check process (See later page)
Unit did not cool, etc.
¡
Is the power on?
¡
Is the thermostat setting correct?
(Not too high?)
¡
Is the unit in a timer operation?
¡
Does user understand function?
etc.
¡
Explain the function of the unit to user.
No need for PCB change
Check further the status when the trouble occured
(such as the timer of occurence, power failures, thun-
der, use status of other electrical appliances, etc).
Clarify the reason for the problem and explain it thor-
oughly to the user.
No need for PCB change
Microcomputer runaway due to power source
conditions is a possible cause.
No need for PCB change
The cause is defective connector contact.
YES
No
No
No
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...