208
SCM-HG
(2 room)
5.5.5
Refrigerant Piping
(1)
Limit
The maximum permissible length of the refrigerant pipes for the outdoor units, and the maximum permissible height difference for
the outdoor units are as shown below.
*
If the total length for all the rooms exceeds the length of chargeless refrigerant
pipe, additionally charge with refrigerant according the item 4.
¡
The diameter of the refrigerant pipe:
¡
Outdoor unit and the total connectable indoor units (class kW):
Liquid side
Gas side
2.2 · 2.5 · 2.8kW
ø 9.52 · t 0.8
3.2 · 4.0kW
ø 12.7 · t 0.8
ø 6.35 · t 0.8
Class of indoor unit (kW)
Diameter of joint pipe
Model
SCM452HENG-L
SCM452CENG-L
Total of indoor units (class kW)
6.5kW
6.5kW
(2)
Connection of refrigerant piping
¡
The service valve corresponding to each indoor unit is as illustrated in the right figure.
¡
Changing the gas side piping size
If the piping connection for the gas side of the outdoor unit does not match the piping size
of the indoor unit, use the parts provided for variable connections to make the joint.
Variable diameter joint (provided): ø9.52
→
ø12.7 (1 piece)
[Examples of use of variable diameter joints]
Connection of indoor unit of Class 4.0 to A unit.
¡
Securely fit the copper packing between the service valve and the variable diameter joint to prevent shifting.
¡
Cover the pipes with tape so that dust and sand do not enter the pipe until they are connected.
[Connection of pipes]
¡
When connecting the pipes to the outdoor unit, be careful about the discharge of fluorocarbon gas or oil.
¡
Make sure to match the pipes between the indoor unit and the outdoor unit with the correct service valves.
(1)
Preparations
¡
Remove the flare nut (from both
liquid and gas sides).
¡
Remove the flare nut (from both
liquid and gas sides).
¡
Fit the removed flare nut to the joint pipe, and then flare it.
A dimensions
Liquid side:
ø 6.35: ø 9 ~ ø 9.5
Gas side:
ø 9.52: ø 13.2 ~ ø 14
ø 12.7: ø 16.2 ~ ø 17
Gas
Gas
side
service
valve
Liquid
Liquid
side
service
valve
Service valve
for room B
Service valve
for room A
ø9.52
ø9.52
ø6.35 pipe
ø12.7 pipe
Indoor unit
4.0 kW class
Liquid side service valve (ø6.35)
Gas side service
valve (ø9.52)
Copper packing
Variable diameter joint (ø9.52–ø12.7)
Service valve
for room A
Indoor
Remove
Push
Outdoor
Remove
Push
90+0.5
˚
A
A
B
C
Length for one indoor unit
Total length for all rooms
Lower installation spot of the indoor unit A
Upper installation spot of the indoor unit B
Maximum height difference of the indoor units C
Length of chargeless refrigerant pipe
Height
difference
Under 25m
Under 30m
Under 15m
Under 10m
Under 10m
20m
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...