19.5.4 Refrigerant piping
(1)
Precautions no refrigerant piping work for prevention against compressor lock
Compressor trouble including lock and motor burn-out is due to faulty parts but mainly concerned in installation and refrigerant
piping conditions, The precautions for refrigerant piping are as belows.
(a)
Be sure to perform brazing while flowing nitrogen.
1)
Without flowing nitrogen gas, a lot of oxide film (CU
2
O) is generated. In particular, in case of for building with many brazed
portions, oxide film is so much generated that this causes a fatal failure in the air conditioning system.
2)
A foreign material (oxide film) causes clogging of the capillary tube or expansion valve, leading to non-cooling (non-
heating), abnormal discharge temperature, compressor lock due to a faulty oil return. In some cases, a lot of foreign materials
block the oil return hole of the accumulator, thereby causing a compressor lock. (This lock trouble may occur repeatedly 2 or
3 times.)
(b)
Don’t admit water (waterdrops, condensation) into the piping.
1)
Use a copper piping that is free from water (waterdrops,
condensation).
2)
Don’t perform refrigerant piping work while it rains.
3)
To suspend outdoor piping work, perform curing to prevent
water admission.
Bad effects of water
•
Capillary tube and expansion valve clogging
•
Refrigerant hydrolysis
→
“Acid” generation
→
Iron/copper corrosion
•
Crystal foreign material (clathrate compound) genera-
tion resulting from reaction on refrigerating machine oil
(c)
Don’t admit dust or foreign particles in the pipe.
Various foreign particles are included in air conditioners that caused trouble. Be careful about them.
(Concrete fragments, cement, sand, paint, metal powder (copper refuse after deburring, etc.), etc.
(d)
Adopt the specified dimensions for pipes.
There will be directly conected to serious
trouble such as compressor lock or burn-
out of the compressor motor.
Too thick:
Improper charge volume
Faulty oil return (insufficient gas flow rate)
Overcharge
Liquid back
Compressor lock
Compressor lock
Faulty oil return
Too long (L):
(e)
Be sure to support the refrigerant piping with support fittings.
1)
The pipe vibrates and expands/shinks during operation. Without proper supports, a load is concentrated partially and cracks
and collapse occur on the piping, thereby causing a unit failure.
2)
A support should be provided at intervals of 2 or 3 m so as not to partially concentrate a load.
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...