450
FDEN-C
11.2.2 Range of usage & limitations
Models
FDENP208, 258 type
FDENP308, 408, 508 type
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Refer to the selection chart
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
Max. 30m
Max. 50m
Max. 10 times/h
Max. 3 minutes
Min. 85% of rating
Rating
±
10%
Max. 20m (Outdoor unit is higher)
Max. 30m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Max. 15m (Outdoor unit is lower)