1082
FDC-HKXR
Is the current
cut function activated?
Is the insullaiton
resistance of the compressor
(1)
proper?
NO
YES
YES
NO
YES
NO
YES
NO
Notes (1) When a short-circuit or ground-fault occurs
in the compressor motor, the current cut
function is also activated.
Notes (1)
If the insulation resistance is 10M
Ω
or more,
it is normal.
Notes (1)
The insulation resistance may considerably
drop depending on the refrigerant volume in
the compressor, but this is not faulty.
(2) 1-2 seconds after a start:
FDCP2001 type: Approx. 32 A
FDCP2501 type: Approx. 37 A
Defective inverter
(Refer to 1090 page)
Defective inverter
(Refer to 1090 page)
Defective compressor
Defective compressor
Disconnect the compressor wiring
Defective inverter
The compressor can operate
Is the output
voltage of the inverter
normal?
Isn't the stating
current
(2)
excessive?
When the compressor wiring is
performed, the unit can operate.
Current cut is indicated and the compressor cannot operate
Frequency
Model
All models
(outdoor unit)
35 Hz
40 Hz
65 Hz
75 Hz
80 Hz
95 Hz
95 ~ 98
104 ~ 107
167 ~ 173
180 ~ 190
195 ~ 197
198 ~ 203
Unit: V (AC)
Inverter output voltage
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...