478
FDKN-H
Item
Models
FDKN (P) 208, 258 type
FDKNP308 type
Indoor return air temperature
(Upper, lower limits)
Refer to the selection chart
Outdoor air temperature
(Upper, lower limits)
Refrigerant line (one way) length
Max. 30 m
Max. 50 m
Vertical height difference between
Max. 20 m (Outdoor unit is higher)
Max. 30 m (Outdoor unit is higher)
outdoor unit and indoor unit
Max. 15 m (Outdoor unit is lower)
Max. 15 m (Outdoor unit is lower)
Power source voltage
Rating
±
10%
Voltage at starting
Min. 85% of rating
Frequency of ON-OFF cycle
Max. 10 times/h
ON and OFF interval
Min. 3 minutes
12.2.2 Renge of usage & limitations