328
FDT(N)-H
FM
01
(Up)
Hi
Hi
Hi
Hi
Hi
Lo
Hi
Fan motor
FDC(P)408, 508 type
Model
FM
02
(Lo)
Hi
OFF
OFF
Hi
OFF
OFF
Hi
C Zone
D Zone
A Zone
E Zone
C Zone
Zone
D Zone
B Zone
E Zone
F Zone
Description of control for fan for outdoor unit
FM
0
Hi
Hi
Hi
Hi
Hi
Lo
Hi
FDC(P)208~308 type
(c)
Operation control function by the outdoor controller (Only FDC(P)208~508 type, FDC808, 1008 type)
1)
Control for outdoor unit fan
a)
Cooling Operation
The speed of the fan for the outdoor unit is controlled by the temperature of the heat exchanger (Tho-R detection) and
the outdoor air temperature (Tho-A).
E Zone
48
Heat exchanger temperature (
°
C)
32
63
57
C Zone
D Zone
B Zone
18
Outdoor air temperature (
°
C)
15
33
31
F Zone
A Zone
C Zone
D Zone
C Zone
D Zone
E Zone
B Zone
A Zone
FM
02
(Right)
OFF
Hi
Hi
OFF
Hi
FM
01
(Left)
Hi
Hi
Hi
Hi
Hi
FM
02
(Lo)
OFF
Hi
Hi
OFF
OFF
FM
01
(Up)
Hi
Hi
Hi
Lo
Hi
FM
0
Hi
Hi
Hi
Lo
Hi
Model
Fan motor
FDC(P)408, 508 type
FDC(P)208~308 type
FDC808,1008 type
Zone
Description of control for fan for outdoor unit
B Zone
11
Outdoor air temperature (
°
C)
9
19
17
E Zone
A Zone
-3
Heat exchanger temperature (
°
C)
0
C Zone
D Zone
b)
Heating Operation
1
Stop control for outdoor fan
When the high pressure switch (63H
2
) operates, the fan for the outdoor unit is stopped to control the high pressure
switch.
63H
2
settings
Models FDC208~1008 type
2.5 OFF/2.06 ON (MPa)
[25.5 OFF/21 ON (kgf/cm
2
)]
2
Tap control for outdoor fan
When the high pressure switch (63H
2
) is closed, the outdoor fan is controlled by the detected heat of the outdoor
heat exchanger thermistor (Tho-R) and the detected heat of the outdoor air temperature thermistor (Tho-A).
Note (1) When the fan for the outdoor unit is started when the outdoor air temperature is more than 12
°
C, it will operate at high speed for 3
seconds and then switch to low speed. After operating a low speed for 4 minutes, it will be transferred to controlled speed.
A Zone
B Zone
C Zone
Zone
D Zone
FM
01
(Left)
Hi
Hi
Lo
Fan motor
FM
02
(Right)
Hi
OFF
OFF
Description of control for fan for outdoor unit
D Zone
48
Heat exchanger temperature (
°
C)
44
C Zone
B Zone
25
Outdoor air temperature (
°
C)
20
A Zone
Models FDC(P)208~508 type
Models FDC808, 1008 type
Models FDCP208~508 type
2.79 OFF/2.26 ON (MPa)
[28.5 OFF/23 ON (kgf/cm
2
)]
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...