FDC-HKX
837
(b) Control of input signal
(Make sure to connect the standard remote control unit. Control of input signal is not available without the standard remote control unit.)
Control of input signal (switch input, timer input) connectors (CNT) are provided on the control circuit board of the indoor unit.
However, when the operation of air conditioner is under the Center Mode, the remote control by CnT is invalid.
(i) At shipping from factory (SW
5-1
on PCB OFF)
1) Input signal to CnT OFF
→
ON [Edge input] Air conditioner ON
2) Input signal to CnT ON
→
OFF [Edge input] Air conditioner OFF
(ii) When SW
5-1
on the PCB of indoor unit is turned on at the field.
Input signal to CnT becomes valid at OFF
→
ON only and the motion of air conditioner [ON/OFF] is inverted.
(21) Multiple Units Control-Simultaneous Control of 16 unit with one remote controller
(a)
Function
Multiple units (even of outdoor different systems, 16 units maximum) can be simultaneously controlled by using a remote
control switch (a special order item). The remote control switch is used to set the “operation mode”, and all the unit can be
operated and stopped at intervals of 0.5 to 1 second in the order of unit number. Thermostat and protective functions of each
unit functions independently.
Note(1) When part of the group gets out of order (the protective device operates), the relevant unit comes to an abnormal stop, but other normal units keep operating.
(b)
Wiring Procedures
(i)
Lay power cable of each unit and signal wire as usual. (Remove the remote control switches from all units excluding only one unit.)
Lay wiring for the remote controller separately from power cable and wires for all other electrical equipment.
(ii)
Arrange the terminal block (X, Y, Z) of the remote controller as shown next page for the simultaneous control, and lay
cross over in each indoor unit.
Notes (1) The overall length of the signal wire shall be less than 1000m.
(2) The length of remote control signal wire and crossover for remote controller between room shall be less than 600m.
CnT Input
A Unit
B Unit
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
CnT Input
A Unit
B Unit
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
ON
OFF
OFF
Outdoor
unit
Indoor
unit
No.1
Indoor
unit
No.2
Indoor
unit
No.3
Indoor
unit
No.16
Outdoor
unit
Signal
wire
(1)
(1)
Signal wire
Remote control
signal wire
(2)
(2)
Remote control
signal wire
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...