FDC-HKX
729
Models FDTJ45HKXE2, 56HKXE2, 71HKXE2
Item
Nominal cooling capacity*
1
W
W
W
CMM
Unit:24 Panel:7
20 1
Hi: 15 Me: 12 Lo: 10
Hi: 16 Me: 13 Lo: 11
25 1
dB(A)
mm
Unit:260 840 840 Panel:30 950 950
Nominal heating capacity*
2
Power source
Net weight
Refrigerant control
Starting method
Fresh air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Room temperature control
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Outdoor units to be combined
Motor
Air flow(Standard)
Exterior dimensions
Height Width Depth
Refrigerant equipment
Heat exchanger
Internal thermostat for fan motor.
Frost protection thermostat
Air handling equipment
Fan type & Q'ty
Operation control
Operation switch
Installation data
Refrigerant piping size
Noise level
Models
FDTJ45HKXE2
(3)
4500
FDTJ56HKXE2
(3)
5600
FDTJ71HKXE2
(3)
7100
5000
6300
1 Phase 220/240V 50Hz
Electronic Expansion Valve +Capillary tube
Line starting
Possible
Long life filter 1(Washable)
Rubber sleeve(for fan motor)
Polyurethane foam
Flare piping
Connectable with VP25
Necessary (both Liquid & Gas lines)
Mounting kit
Decorative Panel
FDCJ140HKXE2B,224HKXE2B,280HKXE2B,FDCP140HKXE2B,224HKXE2B,280HKXE2B
Thermostat by electronics
Turbo fan 1
Liquid line: 6.35(1/4")
Gas line: 12.7(1/2")
Liquid line: 9.52(3/8")
Gas line: 15.88(5/8")
mm(in)
Safety equipment
Remote control switch (Optional:RCD-HKX-S-E2)
Hi: 38 Me: 35 Lo: 34
Louver fine & inner grooved tubing
Hi: 40 Me: 38 Lo: 36
8000
(1) The data are measured at the following conditions.
Notes
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3) The number "2", following the type of each model, represents"CE-marked model" especially for European Union, and for European nations which
require CE marking.
Decorative Panel model (Optional)
Item
Item
Indoor air temperature
Outdoor air temperature
Standards
ISO-T1,JIS B8616
Operation
Model
FDTJ45,56,71 type
T-PSA-32W-E
Panel Part No.
DB
WB
DB
WB
Cooling*
1
27
Heating*
2
20
19
35
7
24
6
kg
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...