225
SCM-CG
(2 room)
Item
Model
SCM452CENG-L
Cooling capacity
W
4500 (2000 ~ 5100)
Power source
1 Phase 220/240V 50Hz
Power consumption
W
1820 (680~2050)
Running current
A
8.4/7.7
Noise level
(4)
dB (A)
46
Exterior dimensions
Height
×
Width
×
Depth
mm
595
×
720
×
290
Color
Stucco white
Net weight
kg
36
Refrigerant equipment
Compressor type & Q’ty
GR5490FD41
×
1
Motor
kW
1.2
Starting method
Direct start
Refrigerant control
Capillary tubes
+
Electric expansion valve
Refrigerant
kg
R22 1.3 (Pre-charged up to the piping length of 20m)
Refrigerant oil
R
0.45 (BARREL FREEZE 32SAM)
Air handling equipment
Fan type & Q’ty
Propeller fan
×
1
Motor
W
24
Air flow (at high)
CMM
26
Shock & vibration absorber
Rubber (for compressor)
Safety equipment
Size
×
Core
×
Number
mm (in)
Liquid line:
φ
6.35 (1/4
″
)
×
2
Gas line:
φ
9.52 (3/8
″
)
×
2
Connecting method
Flare connecting
Attached length piping
—
Insulation
Necessary (Both Liquid & Gas lines)
Power source supply
Terminal block (Screw fixing type)
Size
×
Core number
1.5 mm
2
×
4 cores (Including earth cable)
Connecting method
Terminal block (Screw fixing type)
Accessories (included)
Union : (
φ
9.52
/
φ
12.7)
×
1
Installation sheet, Manual instruction
Indoor units to be combined
Model SCM452CENG-L
Compressor overheat protection, Overcurrent protection
Serial signal error protection
Refrigerant
piping
Connection
wiring
Notes (1) The data are measured at the following conditions.
(2) The values for capacity and power consumption shown in a range ( ) indicate the minimum and maximum of the range.
(3) If the piping length exceeds 20m, additional charging is required. (20g/m)
(4) Expressed in sound pressure level.
SKM22, 25, 40 type
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27ºC
19ºC
35ºC
24ºC
JIS C9612
(2)
Outdoor unit
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...