Check of levelness
Check the levelness as follows. Use a level gauge or adjust the levelness with the following method.
2) Drain pipe
a) Set the drain pipe as a declining gradient (1/50 ~ 1/100) and avoid to cross an over-hand ridge or to allow a trap on the way.
●
Good piping
●
Improper piping
b)
When connecting the drain pipe, avoid undue stress being applied to the pipe at the unit side and fix the pipe at a point as close
as possible to the unit.
c)
A hard vinyl chloride pipe, general VP-25, which is available from markets is ideal for the drain pipe.
d)
When installing the drain pipe, make sure to use the attached drain pipe, drain pipe clamp, and insulation materials for drain
pipe clamp.
●
Insert the drain pipe to the base of outlet.
●
Securely tighten the drain pipe clamp.
●
Make sure to insulate the drain pipe clamp.
e)
When there are plural number of drain pipes, arrange to position the converging pipe at about 100mm below the drain outlet
as shown below. Use a pipe of VP-30 or higher for the converging pipe.
f)
Make sure to provide the thermal insulation for the hard vinyl chloride pipe and drain socket provided indoor.
g)
Air bleed should not be provided in any event.
●
When it is necessary to raise the drain head, the limitation is up to 600mm below the bottom face of ceiling where the unit
is installed. The distance is the dimension of the pipe which is installed perpendicularly from a point close to the output for
drain pipe connection.
Adjust the bottom of main unit
and the water level as shown
below.
Piping side
Vinyl pipe
0~3 mm
Water level
Water injection
Slightly lower the piping side
1.5m~2m
Support fixture
Insulation
materials
Declining gradient
1/100 or more
Trap
Crossing
over-hang ridge
Air bleed
Should be as high as possible.
(Approx. 100 mm)
VP-30
Declining gradient 1/100 or more
295~325
600mm or less
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...