FDC-HKX
885
(b) In the case that there is a wall above the unit
No. of units that can be installed are limited up to 3 units.
(Example : 5HP
×
3 units, 10HP
×
1 units + 5HP
×
1 unit)
(c) Plural units installation (Single crosswise row installtion : No limitation in No. of units)
(d) Plural units installation (Plural installation in lengthwise and crosswise rows)
500 and over
(oblique blow)
150 and over
(side blow)
200 and under
(side blow)
600 and over
5 HP
(One-blower unit)
8 or 10HP
(Two-blower unit)
L1 or L2 0
L1 + L2 500
L1 or L2 350
L1 + L2 750
L2
L1
Wall height H3
Wall height H1
Wall height H2
Wall height H4
(Service space)
Air inlet
L3
Wall height H3
Wall height H1
Wall height H2
Wall height H4
L3
W1
W2
W3
L1
L4
L2
L4
L3
L2
L1
L1 500
L2 0
L3 300
L4 0
L1 500
L2 1,000
L3 300
L4 1,000
H1 1,000
H2 No limitation
H3 700
H4 No limitation
H1 1,000
H2 No limitation
H3 700
H4 No limitation
Note (1) When the wall heights H1 and H3 exceed the limited value, keep dimensions for L1 and L3 as shown below.
L1 = H1 – 500(In the case of side blow, H1 1,000 irrespective of L1 dimension)
L3 = 300 + (H3–700) / 2
However, there is no limitation in wall height H3 if L3 exceeds 600.
Notes (1) Side blow is not allowed.
(2) Secure dimensions L1 and H1 at the service space side. Secure dimensions L3 and H3 at the suction side.
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...