519
FDKN-C
Thermistor
(for frost prevention)
Thermistor
(for detecting dis-
charge pipe temp.)
Thermistor
(for detecting heat
exchanger temp.)
High pressure switch
(for protection)
Preset point of the protective devices
Parts name
Mark
Equipped
unit
Th
I-
R
Tho-D
Tho-R
63H
I
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
All models
OFF 2.5˚C
ON 10˚C
OFF 135˚C
ON 90˚C
OFF 70˚C
ON 60˚C
OFF 3.24MPa (33 Kgf/cm
2
)
ON 2.65MPa (27 kgf/cm
2
)