FDU-H
15.2 SELECTION DATA
15.2.1 Specifications
Model FDU308HEN-SA
Item
Model
FDU308-A
FDC308HEN3
Nominal cooling capacity
(1)
W
7100
Nominal heating capacity
(1)
W
8000
Power source
1 Phase, 220/240V, 50Hz
Cooling input
kW
3.20/3.40
Running current (Cooling)
A
14.8/15.4
Power factor (Cooling)
%
98/92
Heating input
kW
3.06/3.22
Running current (Heating)
A
14.2/14.7
Power factor (Heating)
%
98/91
Inrush current (L.R.A)
A
95
Noise level
dB(A)
41
52
Exterior dimensions
mm
360
×
820
×
830
845
×
880
×
340
Height
×
Width
×
Depth
Net weight
kg
48
74
Refrigerant equipment
–
GT-A5534EN41
×
1
Compressor type & Q’ty
Motor
kW
–
2.5
Starting method
–
Line starting
Heat exchanger
Louver fines & inner grooved tubing
Slitted fins & bare tubing
Refrigerant control
Capillary tube
Refrigerant
R22
Quantity
kg
Holding charged
1.4 [Pre-charged up to the piping length of 5m]
Refrigerant oil
r
–
1.45 (BARREL FREEZE 32SAM)
Defrost control
MC controlled de-icer
High pressure control
High pressure switch
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
2
Propeller fan
×
1
Motor
W
130
×
1
55
×
1
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
20
58
Available static pressure
Pa
Standard: 100 (10), Max: 200 (20)
–
(mmAq)
Fresh air intake
Available
–
Air filter, Q’ty
Field purchased
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
33(Crank case heater)
Operation control
Wired remote control switch
Operation switch
(Optional: RCD-H-E)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Abnormal discharge temperature protection.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit.
Optional parts
–
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 220/240V 50Hz.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1, JIS B8616
Operation data
(3)
FDU308HEN-SA
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...