29
SRK-GZ
S
SRK502Z-L
Note (1) When the start delay of compressor of indoor unit controller is actuated and the operation is reset, it takes 2 minutes and 55 seconds.
When stopped by indoor unit controller
When stopped or reset by outdoor unit protective function
Function
Operation
Heating, heating
Cooling, cooling
Heating, heating
Cooling, cooling
oriented dehumidifying
oriented dehumidifying
oriented dehumidifying
oriented dehumidifying
Stop
Full stop
Stop
Full stop
Stop
Restart
Stop
Restart
(0 rps command)
(0 rps command)
(0 rps command)
(0 rps command)
Inverter
frequency
Indoor
fan
Indoor
power
relay
Outdoor
fan
4-way
valve
(Command
frequency)
0
(Frequency
dependent)
OFF
ON
OFF
3 min.
(1)
3 min.
(1)
2 min.
2 min.
55 sec.
55 sec.
Hot keep
2 min.55sec.
ON
OFF
ON
OFF