FDC-HKX
753
Item
Models
FDR, FDUM Series
FDR, FDUM Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.11/0.13
0.51/0.56
0.09/0.11
0.41/0.46
0.14/0.16
0.63/0.67
0.15/0.17
0.68/0.71
0.16/0.19
0.73/0.79
0.24/0.28
1.07/1.17
0.28/0.32
1.28/1.32
22
28, 36
45
56
71
90
112
140
Item
Models
FDTS Series
FDTS Series
Power input (kW)
Running current (A)
0.07/0.08
0.33/0.36
22
28
36
0.09/0.11
0.43/0.46
45
(220 V/240 V)
0.12/0.15
0.58/0.63
71
Item
Models
FDK Series
FDFL, FDFU Series
FDK, FDFL, FDFU Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.06/0.07
0.31/0.33
0.05/0.06
0.26/0.28
0.08/0.09
0.36/0.39
0.09/0.11
0.41/0.48
0.09/0.10
0.41/0.42
0.09/0.10
0.40/0.41
0.09/0.10
0.40/0.41
28
22
36
45
56
71
28
45, 56
71
Item
Models
FDE Series
FDE Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.10/0.11
0.43/0.46
0.12/0.15
0.58/0.63
36
45
56
71
0.20/0.24
0.90/0.98
112
0.24/0.29
1.10/1.20
140
Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616 “UNITARY AIR-CONDITIONERS”
(2) The values shown in the above table are common to both cooling and heating operations.
(c)
Calculation of total operation characteristics
Since the operation characteristics of series Multi-KX depend on combination of indoor unit, calculate the total operation characteristics
of the system by using the formulas below according to specifications of each indoor unit or outdoor unit.
1) Total power input
Total power input (kW) = Power input of outdoor unit +
∑
(Power input of indoor unit)
2) Total running current
Total running current (A) = Running current of outdoor unit + [
∑
(Running current)
×
2/3]
3) Total power factor
Total power factor (%) = [Total power input (W) /
√
—
3
×
Total running current (A)
×
Power source]
×
100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(Conditions)
Operation Voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit·······························Outdoor unit: FDCJ224HKXE2B
×
1 unit
Indoor unit: FDTJ71HKXE2
×
2 units
FDTJ45HKXE2
×
2 units
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...