SCM-HG
(4 room)
154
(d)
Use the power supply wires specified below. Different wires may cause heat generation and fire. Do not to use unspecified
wires.
Never bundle, wind or treat the power wires. Otherwise, heat or fire may be generated.
[POWER SUPPLY CODE]
CENELEC code for cables required field cables.
H05RNR3G 4.0
(e)
After connecting the power supply wires, make sure to secure the wires with wiring clamps.
(2)
Connecting the outside/inside crossover wires
(a)
Ensure that crossover wiring is matched with crossover piping in A,B and C rooms.
(b)
The length of the crossover wires should be under 25 m. If it longer than 25 m, signal errors between the units may occur and
cause the operation to shut down.
(c)
Use the crossover wires specified below. Different wires may cause heat generation and fire. Do not to use unspecified wires.
[INTERCONNECTING WIRING CODE]
CENELEC code for cables required field cables.
H05RNR4G 1.5
(d)
Make sure the terminal numbers on the terminal board of the indoor and outdoor connections are correct.
(e)
After connecting the crossover wires to the terminal board, use wiring clamps to secure the wiring.
4.5.5
Refrigerant Piping
(1)
Limit
The maximum permissible length of the refrigerant pipes for the outdoor units, and the maximum permissible height difference for
the outdoor units are as shown below.
* If the total length for all the rooms exceeds the length of chargeless refrigerant pipe, additionally charge with refrigerant
according the item 6.
¡
The diameter of the refrigerant pipe:
¡
Outdoor unit and the total connectable indoor units (class kW):
Lower installation spot of the indoor unit A
Upper installation spot of the indoor unit B
Maximum height difference of the indoor units C
Length for one indoor unit
Total length for all rooms
Length of chargeless refrigerant pipe*
SCM802HENG-L SCM1002HENG-L
under 30m
under 80m
under 15m
under 10m
under 25m
50m
Height
difference
Liquid side
Gas side
2.2 · 2.5 · 2.8kW
ø 9.52 · t 0.8
3.2 · 4.0 · 5.0kW
ø 12.7 · t 0.8
ø 6.35 · t 0.8
Class of indoor unit (kW)
Diameter of joint pipe
Use cables for interconnection wiring to avoid loosening of the wires.
CENELEC code for cables Required field cables.
H05 RNR3G4.0 (Example)
H
Harmonized cable type
05
300/500 volts
R
Natural-and/or synth. rubber wire insulation
N
Polychloroprene rubber conductors insulation
R
Stranded core
3
Number of conductors
G
One conductor of the cable is the earth conductor (yellow/green)
4.0
Section of copper wire (mm
2
)
A
B
C
Model
SCM802HENG-L
SCM1002HENG-L
Total of indoor units (class kW)
12.0kW
13.6kW
SCM802HENG-L
SCM1002HENG-L
30A
40A
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...