(11) Cooling operation control at lower outdoor air temperature (down to –5˚C)
(a) This control starts 1 minute after starting compressor during cooling or dehumidifying operation, controls the outdoor fan at the
outdoor temperature (Tho-A) being below 22˚C and enables the cooling operation.
(b) Outdoor fan control
Outdoor fan tap
140 model
224,280 models
(c) In cases of 224 and 280 only, the low outdoor air cooling control is releases temporarily when the number of operating compres-
sors is changed (1 unit
→
2 unit) and the outdoor fan is operated in the Hi mode. The low outdoor air temperature cooling control
becomes effective 2 minutes later.
(12) Snow protection fan control
If J6 on the outdoor unit PCB is opened, the outdoor fans on the units which have been stopped with the total or error stop are
operated in the Hi mode once at every 10-minute while the outdoor temperature is lower than 3˚C.
(13) Forced heating/cooling operation
With this control, SW3-7 on the outdoor unit PCB is turned on and CnG (equipped with short circuit pin) is shorted or opened so
as to forcibly determine whether the indoor unit is operated for cooling or heating. If any operation mode other than the forcible
mode is commanded from the indoor unit, the mode unmatch message is displayed on the remote controller or others and the
operation enters in the blowing mode.
Note (1) SW-7 is at OFF and CnG is open at the shipping from factory.
• Control A
For 140 : OFF, 1 ~ 2 speed control ranges
For 224, 280 : OFF, 1 ~ 3 speed control ranges
• Control B
For 140 : 1 ~ 3 speed control ranges
For 224, 280 : 1 ~ 4 speed control ranges
Fan tap
3 speed 2 speed 1 speed
OFF
FM
01
Hi
Me
Lo
OFF
Fan tap
4 speed 3 speed 2 speed 1 speed
OFF
FM
01
Hi
Hi
Me
Lo
OFF
FM
ON
OFF
OFF
OFF
OFF
(External air temperature)
SW3-7
CnG
Operation
OFF
Open/short
Normal operation
ON
Open
Cooling
Short
Heating
ON
OFF
Control A
Outdoor air temperature (˚C)
Control B
Outdoor fan control effective
Outdoor air temperature (˚C)
02
Disabled
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...