FDC-HKX
738
Models FDRJ71HKXE2, 90HKXE2
Item
Nominal cooling capacity*
1
Panel model (Option)
Air inlet panel
Silent panel
R-PNLS-36W-E
R-PNLC-36W-E
R-PNLS-36W-E
R-PNLC-36W-E
Canvas panel
Canvas panel
Silent panel
W
W
W
CMM
kg
Pa (mmAp)
Standard:45 (4.5), Hi speed:80 (8.0)
Unit:35
Panel:8
Unit:35
Panel:6
Unit:35
Panel:8
Unit:35
Panel:6
Hi: 18 Me: 16 Lo: 14
Hi: 20 Me: 18 Lo: 15
90 1
dB(A)
mm
Unit:355 950 635
Panel:10 1240 750
Nominal heating capacity*
2
Power source
Net weight
Refrigerant control
Starting method
Fresh air intake
Air filter Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Room temperature control
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Outdoor units to be combined
Motor
Air flow(Standard)
Exterior dimensions
Height Width Depth
Refrigerant equipment
Heat exchanger
Internal thermostat for fan motor.
Frost protection thermostat
Air handling equipment
Fan type & Q'ty
Available static pressure
( at Me)
Operation control
Operation switch
Installation data
Refrigerant piping size
Noise level
Models
FDRJ71HKXE2
(4)
7100
FDRJ90HKXE2
(4)
9000
8000
1 Phase 220/240V 50Hz
Electronic Expansion Valve +Capillary tube
Line starting
Side or back
Long life filter 1(Washable)
Rubber sleeve(for fan motor)
Polyurethane foam
Flare piping
Connectable with VP25
Necessary (both Liquid & Gas lines)
Mounting kit
Silent panel, Canvas panel, Canvas duct
FDCJ140HKXE2B,224HKXE2B,280HKXE2B,FDCP140HKXE2B,224HKXE2B,280HKXE2B
Thermostat by electronics
mm(in)
Safety equipment
Remote control switch (Optional:RCD-HKX-E2)
Hi: 43 Me: 40 Lo: 37
Hi: 44 Me: 41 Lo: 38
Hi: 43 Me: 40 Lo: 37
Hi: 44 Me: 41 Lo: 38
Louver fins & inner grooved tubing
10000
Unit:355 950 635
Panel:10 1064 585
Unit:355 950 635
Panel:10 1064 585
Unit:355 950 635
Panel:10 1240 750
100 1
(1)The data are measured at the following conditions.
Notes
(2)This packaged air-conditioner is manufactured and tested in conformity with the following standard.
JIS B8616"UNITARY AIR-CONDITIONERS"
(3)Canvas panel is used in combination with following canvas duct
Canvas duct:
(4)The number "2",following the type of each model,represents"CE-marked model"especially for European Union, and for European nations which
require CE marking.
(5)Add the canvas duct lenght to the unit height for the canvas type.
Item
Indoor air temperature
Outdoor air temperature
Standards
ISO-T1,JIS B8616
Operation
DB
WB
DB
WB
Cooling*
1
27
Heating*
2
20
19
35
7
24
6
Centrifugal fan 2
Liquid line: 9.52(3/8"),Gas line: 15.88(5/8")
HA01490
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...