1033
FDC-HKXR
(3)
Operations of major functional items under each operation mode
Notes (1)
: ON,
: OFF,
/
: ON or OFF
(2) Cooling and heating also include auto mode.
(3) Off if jumper wire (J3) is short circulated (factory setting) and open.
(4)
Cooling operation
(a) Cooling
1) If the sum of selected and required frequencies is not larger than the maximum frequency, the required frequencies listed in the
following table apply. If the sum of required frequencies is larger than the maximum frequency, the required frequencies divided
proportionally apply.
Frequency bands for indoor unit models
Notes (1) Frequency during cooling is 45 Hz.
(2) The required frequency is counted in the unit of 5 Hz and the selected frequency in the unit of 1 Hz.
2) This indoor unit electronic expansion valve (EEV) controls opening of each indoor unit corresponding to decision frequency.
Also, the thermostat is sampled in pitch of 20 second.
Operation mode
Functional item
Cooling
Heating
Dehumidify
Thermostat ON Thermostat OFF
Thermostat ON Thermostat OFF
Defrost
Indoor unit fan
Indoor unit electronic
expansion valve
Compressor
Outdoor unit fan
Drain motor
Solenoid valve (20VU)
Solenoid valve (20 VF)
Four-way valve (20 SL,S)
Solenoid valve (SV1, L,S)
Remote controller
command
According to deter-
mined frequency
/
/
Remote controller
command
Fully closed
Remote controller
command
Fully closed
Remote controller
command
According to deter-
mined frequency
/
/
Intermittent
operation
Fully closed
→
Fully open
→
/
According to deter-
mined frequency
/
/
/
/
22 model 28 model 36 model 45 model 56 model 71 model 90 model 112 model 140 model
10 ~ 15
10 ~ 20
10 ~ 25
10 ~ 25
15 ~ 30
15 ~ 40
15 ~ 50
35 ~ 60
35 ~ 70
5 ~ 15
5 ~ 20
5 ~ 25
5~ 25
5 ~ 30
5 ~ 40
5 ~ 50
5 ~ 60
5 ~ 70
(b) Cooling thermostat off
(i) When all thermostata of indoor unit in a module are turned off, the indoor units operate in the cooling thermostat off
mode per outdoor unit module.
(ii) When the decision frequency to indoor units is less than 5Hz, or when the demand frequency reaches to the OFF area
according to fuzzy operation, the ndoor units will select the cooling thermostat of mode.
fan
Individual definitions
Individual definitions
(2)
Automatic Operation
Once the [Auto] mode is selected by remote control, the operating mode is automatically selected according to the setting temperature
and the intake air temperature of the indoor unit and cooling or heating operation is performed. The determination is performed
when the thermostat has been in the OFF mode for 10 minutes or more continuously.
Notes (1) No determination is made if the mode setting is cooling, dehumidify or heating
and the cooling and heating thermostats have been in the off mode for 10 minutes
in the automatic operation mode.
(2) If set to automatic operation mode when the intake temperature is within
±
2 ˚C in
relation to the setting temperature, the same operation as the previous automatic
operation will be performed. (Note that it will be the heating mode when first
turned on after the power has been turned off.)
-2
+2
Heating operation
Cooling operation
Room temperature setting
Room temperature (detected atTh
I
-A) (deg.)
Model (Indoor)
Category
All series
Required frequency (Hz)
Selected frequency (Hz)
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...