FDC-HKX
847
2)
When connecting the drain pipe to the unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also,
fix the piping at a point as close as possible to the unit.
3)
For drain pipe, use hard PVC ganeral purpose pipe VP-25 (I.D.1'') which can
be purchased locally. When connecting, insert a PVC pipe end securely into
the drain socket before tightening securly using the attached drain hose and
clamp. Adhesive must not be used connection of the drain socket and drain
hose (accessory).
Drain socket
Level difference part
Drain hose
Joint for VP-25
(local procurement)
Pipe cover (small)[insulation]
(accessory)
Drain socket
Unit
Clamp
(accessory)
Drain hose
(accessory)
Adhesion
VP-25
(local procurement)
Pipe cover [insulation]
(local procurement)
Pipe cover (large)[insulation]
(accessory
4)
When constructing drain piping for several units, position the common pipe about 100mm below the drain outlet of each unit
as shown in the sketch below. Use VP-30 or thicker pipe for this pupose.
Secure the elevation as high as possible
(approx. 100 mm)
VP30
A downhill grade of
1/100 or more
5)
Be sure to provide heat insulation to hard PVC pipes of indoor placement.
6)
Do not ever provide an air vent.
7)
The height of the drain head may be elevated up to a point 750mm above the ceiling and, when an obstacle exists in the ceiling
space, elevate the piping to avoid the obstacle using an elbow or corresponding gadget. When doing this, if the stretch for the
needed height is too high, the back-fiow quantity of drain at the time of interruption of the operation gets too much and it may
cause overflow at the drain pan. Therefore, make the height of the drain pipe withing the distance given in the drawing below.
8)
Avoid positioning the drain piping outlet at a place where ganeration of odor may be stimulated. Do not lead the drain piping
direct into a sewer from where sulfur gas may generate.
When Using a Natural Drain Port
1) Remove the heat insulating material and rubber plug of the natural drain port.
2) By using the natural drain connecting tube (option), connect the drain pipe (VP-20) and completely clamp it with a clamp.
Note (1) If the drain pipe is directly connected to the natural drain port, the drain pan becomes unremovable.
3) Disconnect the connector CNR (blue, 2P) for the drain motor.
295~325
Drain hose (accessory)
Joints for VP-25 (local procurement)
100 mm or less
750 mm or less
Summary of Contents for SRRM40HENG-L
Page 1: ...MITSUBISHI DAIYA 2000 AIR CONDITIONING HEAT PUMP MACHINERY HANDBOOK ...
Page 52: ...50 SRK GZ MEMO ...
Page 94: ...92 SRK H MEMO ...
Page 104: ...102 102 SRK C MEMO ...
Page 180: ...178 SCM HG 4room MEMO ...
Page 222: ...220 SCM HG 2room MEMO ...
Page 234: ...232 SCM CG 2room MEMO ...
Page 266: ...SCM C 264 MEMO ...
Page 406: ...404 FDT N C MEMO ...
Page 442: ...440 FDEN H MEMO ...
Page 470: ...468 FDEN C MEMO ...
Page 504: ...502 FDKN H MEMO ...
Page 580: ...578 FDR H MEMO ...
Page 698: ...696 V MULTI Models FDR258 A 308 A ...
Page 724: ...722 V MULTI MEMO ...
Page 1094: ...1092 FDC HKXR MEMO ...