387
Appendix
Set a home preset
Axis-specific parameter No. 12, “Home preset value”
No.
Parameter name
Default value
Input range
Unit
12
Home preset value
0
-99999999 ~ 99999999
0.001 mm
z
Explanation of setting
Set a value indicating where the actuator should be upon completing home return.
(Normally, the actuator should be at 0-mm coordinate upon completing home return.)
z
Set value
Unit: 0.001 mm
Example 1:
“Do not set” a home preset value
Home
return
complete
o
[0.000] mm is displayed.
Example 2:
Set “3000” as a home preset value
Home
return
complete
o
[3.000] mm is displayed.
z
Note
Take note that when a home-return preset value is set, the effective stroke will also change. In
particular, the stroke will decrease if the preset position is on the positive side of the default home.