199
Part 2 Programs
1.16 System Information Acquisition
z
AXST (Get axis status)
Command, declaration
Extension condition
(LD, A, O, AB, OB)
Input condition
(I/O, flag)
Command,
declaration
Operand 1
Operand 2
Output
(Output, flag)
Optional Optional
AXST
Variable
number
Axis
number
CP
[Function]
Store in the variable specified in operand 1 the status (axis error number) of the axis
specified in operand 2.
(Note 1)
If the obtained result is “0,” it means no axis error is present.
(Note 2)
Since the error lists are written in hexadecimals, they must be converted to decimals.
[Example]
AXST
1
2
Read the error number for axis 2 to variable 1.
If 3188 (decimal) is stored in variable 1 after the execution of this command:
3188
y
16 = 199 ,,,4
199
y
16 = 12 (= C) ,,,7
3188 = 12 (= C) X 16
2
+ 7 X 16
2
+ 4
= C74 (HEX) (Hexadecimal number)
Therefore, an “Error No. C74, Actual-position soft limit over error” is present.
Summary of Contents for PSEL
Page 2: ......
Page 10: ......
Page 18: ...8 Part 1 Installation ...
Page 37: ...27 Part 1 Installation 2 2 axis specification with battery ...
Page 382: ...372 Appendix Micro cylinder RCL Series Current limiting value ratio Push force N ...
Page 476: ...466 Appendix ...
Page 480: ...470 ...
Page 485: ...475 ...
Page 487: ...INTELLIGENT ACTUATOR SEL Language Programming Manual Eighth Edition ...
Page 488: ......
Page 490: ......
Page 494: ......
Page 518: ...24 ...
Page 526: ...32 ...
Page 831: ... 11 Actuator Control Declaration 337 Example DFIF 1 170 ...
Page 1060: ......
Page 1061: ......