102
Part 2 Programs
z
TRAN (Copy)
Command, declaration
Extension condition
(LD, A, O, AB, OB)
Input condition
(I/O, flag)
Command,
declaration
Operand 1
Operand 2
Output
(Output, flag)
Optional Optional
TRAN
Variable
number
Variable
number
ZR
[Function]
Assign the content of the variable specified in operand 2 to the variable specified in
operand 1.
The output will turn ON when 0 is assigned to the variable specified in operand 1.
[Example 1]
TRAN
1
2
Assign the content of variable 2 to variable 1.
LET
1
*2
A LET command of the same effect as the above
operation
[Example 2]
LET
3
4
Assign 4 to variable 3.
LET
4
10
Assign 10 to variable 4.
TRAN
1
*3
Assign the content of variable 3 (which is variable
4, or 10) to variable 1.
(Note) When data in a real variable is assigned to an integer variable, all decimal fractions are
rounded to the nearest integer.
LET
100
13.5
Assign 13.5 to real variable 100.
TRAN
1
100
Assign 14, which is a rounded result of the content
of real variable 100 (13.5), to integer variable 1.
Summary of Contents for PSEL
Page 2: ......
Page 10: ......
Page 18: ...8 Part 1 Installation ...
Page 37: ...27 Part 1 Installation 2 2 axis specification with battery ...
Page 382: ...372 Appendix Micro cylinder RCL Series Current limiting value ratio Push force N ...
Page 476: ...466 Appendix ...
Page 480: ...470 ...
Page 485: ...475 ...
Page 487: ...INTELLIGENT ACTUATOR SEL Language Programming Manual Eighth Edition ...
Page 488: ......
Page 490: ......
Page 494: ......
Page 518: ...24 ...
Page 526: ...32 ...
Page 831: ... 11 Actuator Control Declaration 337 Example DFIF 1 170 ...
Page 1060: ......
Page 1061: ......