188 Parameters
Defines the maximum for the frequency actually arriving at
frequency input 1 (DI5 or DI6 when it is used as a frequency
input). See parameter
.
16000 Hz
0 … 16000 Hz
Maximum frequency for frequency input 1 (DI5 or DI6).
1 = 1 Hz
Defines the value that is required to correspond internally to
the minimum input frequency defined by parameter
. See diagram at parameter
0.000
-32768.000…
32767.000
Value corresponding to minimum of frequency input 1.
1 = 1
Defines the value that is required to correspond internally to
the maximum input frequency defined by parameter
. See diagram at parameter
50.000
-32768.000…
32767.000
Value corresponding to maximum of frequency input 1.
1 = 1
12
Configuration of standard analog inputs.
The true readings of the analog inputs can be overridden for
e.g. testing purposes. A forced value parameter is provided
for each analog input, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note:
and
) have no effect on forced AI values
(parameters
Note:
Boot and power cycle reset the force selections
(parameters
and
0b0000
0b000...0b1111
Forced values selector for analog inputs AI1 and AI2.
1 = 1
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The supervision applies a margin of 0.5 V or 1.0 mA to the
limits. For example, if the maximum limit for the input is
7.000 V, the maximum limit supervision activates at 7.500 V.
The inputs and the limits to be observed are selected by
parameter
No action
No action taken.
0
Fault
Drive trips on
.
1
Warning
Drive generates an
warning.
2
Last speed
Drive generates a warning (
) and freezes
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
1 = Force AI1 to value of parameter
1
1 = Force AI2 to value of parameter
2…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...