460 Fieldbus control through the embedded fieldbus interface (EFB)
Exception codes
The table below shows the Modbus exception codes supported by the embedded
fieldbus interface.
2Bh / 0Eh
Encapsulated Interface
Transport
Supported subcodes:
• 0Eh Read Device Identification: Allows reading the
identification and other information.
Supported ID codes (access type):
• 00h: Request to get the basic device identification
(stream access)
• 04h: Request to get one specific identification
object (individual access)
Supported Object IDs:
• 00h: Vendor Name (“ABB”)
• 01h: Product Code (for example, “ASCLx or
ASCDx”)
• 02h: Major Minor Revision (combination of contents
of parameters
and
• 03h: Vendor URL (“www.abb.com”)
• 04h: Product name: (“ACS560”).
Code
Name
Description
01h
ILLEGAL FUNCTION
The function code received in the query is not an
allowable action for the server.
02h
ILLEGAL ADDRESS
The data address received in the query is not an
allowable address for the server.
03h
ILLEGAL VALUE
The requested quantity of registers is larger than the
device can handle. This error does not mean that a
value written to the device is outside of the valid
range.
04h
DEVICE FAILURE
An unrecoverable error occurred while the server was
attempting to perform the requested action. See
section
Error code registers (holding registers
on page
Code
Function name
Description
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...