350 Parameters
Specifies the maximum wear imbalance, or difference in
running times between any motor, used by the
setting of parameter
10.00 h
0.00…1000000.00
h
Time.
1 = 1 h
Upper speed limit for the Autochange to occur. The
Autochange occurs when:
• the condition defined in
is fulfilled
and,
• the speed of the drive motor
is below
the speed limit defined in this parameter.
Note:
When the value is selected as 0%, this speed limit
check is disabled.
100.0%
0.0…300.0%
Speed/frequency in percentage of the nominal speed or
frequency of the drive motor.
1 = 1%
Selects whether only auxiliary motors or all motors are
included in the Autochange function.
All motors
All motors, including the one connected to the drive
participates in the autochange. The Autochange logic will
connect the drive to each of the motors according to setting of
parameter
Note:
The first motor (PFC1) also requires the appropriate
hardware contactor connections and PFC1 must be defined
in one of the relay output source parameters.
0
Aux motors only
Only auxiliary (direct-on-line) motors are affected by the
autochange function.
Note:
PFC1 refers to the motor that is fixed to the drive and
must not be selected in any of the relay output source
parameters. Only the starting order of the auxiliary motors will
be rotated.
1
Defines if the PFC motor 1 can be started. An interlocked
PFC motor cannot be started.
0 = Interlocked (not available), 1 = Available.
Available.
PFC motor is
available
Interlocked. PFC
motor is not in use
PFC motor is interlocked and not available.
0
Available. PFC
motor is available
PFC motor is available.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Timed function 1
8
Timed function 2
9
Timed function 3
10
Source selection (see
). -
See parameter
Available.
PFC motor is
available
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...