Parameters 369
Reduced
Reduced ID run. This mode should be selected instead of the
or
ID Run if
• mechanical losses are higher than 20% (ie. the motor
cannot be de-coupled from the driven equipment), or if
• flux reduction is not allowed while the motor is running (ie.
in case of a motor with an integrated brake supplied from
the motor terminals).
With this ID run mode, the resultant motor control in the field
weakening area or at high torques is not necessarily as
accurate as motor control following a Normal ID run. Reduced
ID run is completed faster than the Normal ID Run (< 90
seconds).
Note:
Check the direction of rotation of the motor before
starting the ID run. During the run, the motor will rotate in the
forward direction.
WARNING!
The motor will run at up to approximately
50…100% of the nominal speed during the ID run.
ENSURE THAT IT IS SAFE TO RUN THE MOTOR
BEFORE PERFORMING THE ID RUN!
2
Standstill
Standstill ID run. The motor is injected with DC current. With
an AC induction (asynchronous) motor, the motor shaft is not
rotated.
Note:
This mode should be selected only if the
,
ID run is not possible due to the
restrictions caused by the connected mechanics (e.g. with lift
or crane applications).
3
Advanced
Advanced ID run. Only for frames R6…R8.
Guarantees the best possible control accuracy. The ID run
takes a very long time to complete. This mode should be
selected when top performance is needed across the whole
operating area.
Note:
The driven machinery must be de-coupled from the
motor because of high torque and speed transients that are
applied.
WARNING!
The motor may run at up to the maximum
(positive) and minimum (negative) allowed speed
during the ID run. Several accelerations and
decelerations are done. The maximum torque, current and
speed allowed by the limit parameters may be utilized.
ENSURE THAT IT IS SAFE TO RUN THE MOTOR BEFORE
PERFORMING THE ID RUN!
6
Adaptive
Adaptive ID run. Initially, drive runs in Standstill ID run mode
and then refines the motor parameters during the normal
operation. This helps to achieve more optimal performance.
Note:
This is applicable for R0...R5 frames only.
7
Shows the type of ID run that was performed last. For more
information about the different modes, see the selections of
parameter
.
None
No ID run has been performed.
0
Normal
ID run.
1
Reduced
ID run.
2
Standstill
ID run.
3
Advanced
ID run.
6
Adative
ID run.
7
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...