144 Control macros
Default control connections for the Pharma macro
X1
Reference voltage and analog inputs
1
SCR
Signal cable shield (screen)
2
AI1
External speed reference: 0…10 V
1) 4) 7)
:
see
3
AGND
Analog input circuit, common
4
+10V
10 V DC reference voltage
5
AI2
Not configured
6
AGND
Analog input circuit, common
7
AO1
Motor speed used: 0…20 mA
8)
:
see
8
AO2
Motor current: 0…20 mA
8)
:
see
9
AGND
Analog output circuit common
X2, X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 VDC, max. 250 mA
3)
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Pulse start
7)
: see
14
DI2
Stop
7)
:
see
15
DI3
Constant speed sel 1
7)
:
see.
16
DI4
Constant speed sel 2
7)
:
see.
17
DI5
Constant speed sel 3
7)
: see.
4)
18
DI6
Not configured
X6, X7,
Relay outputs
19
RO1C
Enabled
8)
: see.
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
8)
: see.
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault
8)
: see.
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
Built-in fieldbus
29
B+
Internal Modbus RTU (EIA-485), see
control through the embedded fieldbus
30
A-
31
DGND
(Frame R0...R2)
S100
TERM&BIAS
Termination resistor and bias resistor switch
(Frame R3...R8)
S100
TERM
Termination resistor switch
S200
BIAS
Bias resistor switch
X4
Safety torque off
R0...R2 R3...R8
33
-
OUT1
Safety torque off function. Factory connection.
Both circuits must be closed for the drive to
start. See
Safe torque off function
in the drive
hardware
manual.
34
SGND
OUT2
35
OUT1
SGND
36
IN1
IN1
37
IN2
IN2
X10
24 V AC/DC (frames R6...R8 only)
40
24 V AC/DC- in
24V AC/DC input, for control unit power supply
when external main power is disconnected.
41
24 V AC/DC+ in
X11
Redundant auxiliary voltage output
42
+24 V
Aux. voltage 24 V DC, max. 250 mA
3)
43
DGND
Aux. voltage output common
44
DCOM
Digital input common for all
5)
5)
Max.
500 ohm
6)
1…10 kohm
R3...R8
5) 9)
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...