348 Parameters
Defines the stop speed (Hz/rpm) for the second auxiliary
motor. See parameter
Vector:
800 rpm;
Scalar 25 Hz;
30 Hz
(
Defines the stop speed (Hz/rpm) for the third auxiliary motor.
See parameter
Vector:
800 rpm;
Scalar 25 Hz;
30 Hz
(
Defines a start delay for auxiliary motors. See parameter
.
10.00 s
0.00…12600.00 s
Time delay.
1 = 1 s
Defines a stop delay for auxiliary motors. See parameter
.
10.00 s
0.00…12600.00 s
Time delay.
1 = 1 s
Hold time for auxiliary motor switch-on. See parameter
0.00 s
0.00…1000.00 s
Time.
1 = 1 s
Hold time for auxiliary motor switch-off. See parameter
.
0.00 s
0.00…1000.00 s
Time.
1 = 1 s
Start delay for the motor that is directly controlled by the drive.
This does not affect the starting of the auxiliary motors.
WARNING!
There must always be a delay set if the
motors are equipped with star-delta starters. The
delay must be set longer than the time setting of the
starter. After the motor is switched on by the relay output of
the drive, there must be enough time for the star-delta starter
to first switch to star and then back to delta before the motor
is connected to the drive.
0.50 s
0.20…600.00 s
Time delay.
1 = 1 s
Defines the acceleration time for the drive motor speed
compensation, when an auxiliary motor is stopped. This ramp
time is also used for the drive motor to accelerate after an
autochange has occurred.
The parameter sets the ramp-up time as seconds from zero
to maximum frequency (not from the previous reference to
the new reference).
1.00 s
0.00…1800.00 s
Time.
1 = 1 s
Defines the deceleration time for the drive motor speed
compensation, when an auxiliary motor is started. This ramp
time is also used for the drive motor to decelerate after an
autochange has occurred.
The parameter sets the ramp-up time as seconds from
maximum to zero frequency (not from the previous reference
to the new reference).
1.00 s
0.00…1800.00 s
Time.
1 = 1 s
No.
Name/Value
Description
Def/FbEq16
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...