244 Parameters
Mul (ref1 × ref2)
The multiplication of the reference sources is used as
frequency reference 1.
3
Min (ref1, ref2)
The smaller of the reference sources is used as frequency
reference 1.
4
Max (ref1, ref2)
The greater of the reference sources is used as frequency
reference 1.
5
Determines how constant frequencies are selected, and
whether the rotation direction signal is considered or not
when applying a constant frequency.
0b0001
0b000...0b1111
Constant frequency configuration word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Information
0
Const freq
mode
1 = Packed: 7 constant frequencies are selectable using the three
sources defined by parameters
and
.
0 = Separate: Constant frequencies 1, 2 and 3 are separately activated
by the sources defined by parameters
and
respectively. In case of conflict, the constant frequency with the smaller
number takes priority.
1
Direction
enable
1 = Start dir: To determine running direction for a constant speed, the
sign of the constant speed setting (parameters
) is
multiplied by the direction signal (forward: +1, reverse: -1). This
effectively allows the drive to have 14 (7 forward, 7 reverse) constant
speeds if all values in
…
are positive.
WARNING:
If the direction signal is reverse and the active
constant speed is negative, the drive will run in the forward
direction.
0 = Accord Par: The running direction for the constant speed is
determined by the sign of the constant speed setting (parameters
…
2
Frequency step Frequency step: 1 = Freq step enable; 0 = Freq step disable
3…15
Reserved
Summary of Contents for ACS560
Page 1: ...ABB GENERAL PURPOSE DRIVES ACS560 standard control program Firmware manual...
Page 4: ...4...
Page 30: ...30 Start up control with I O and ID run...
Page 32: ...32 Using the control panel...
Page 100: ...100 Program features...
Page 153: ...Control macros 153...
Page 160: ...160...
Page 374: ...374 Parameters...
Page 408: ...408 Additional parameter data...
Page 466: ...466 Fieldbus control through the embedded fieldbus interface EFB...
Page 504: ...504 Control chain diagrams...
Page 508: ...508 Parameterization with drive composer...
Page 512: ...512 Parameterization with automation builder drive manager...